Emin for unbraced glulam column design

Question: Per the 2005 NDS®, which Emin should be used for the design of an unbraced structural glued laminated timber column under purely axial load. Since Emin is now used in the calculation for CP and there is no Eaxial min in the NDS Supplement for glulam, which Emin should be used - Ex min or Ey min?


Answer: Check both the weak axis and the strong axis and use the corresponding Emin for each axis. Eaxial is the longitudinal modulus of elasticity and is used only for calculations involving the change in longitudinal dimension of the member. For axial buckling calculations, Ex min or Ey min should be used as appropriate.