| Wood-frame
walls and floors offer designers a unique opportunity to provide structures
with economy as well as proven energy performance. Where these assemblies
are required by the building codes to achieve a minimum fire endurance
rating, a wide range of options for design exists.
BUILDING CODE
REQUIREMENTS
Many sources are available for obtaining information on the fire endurance of assemblies. Generally, publications from recognized testing laboratories are the source for fire endurance ratings of assemblies that have been tested. Building codes and regulators accept assemblies included in these publications as having the identified fire endurance rating. Until recently, building officials did not recognize methods for determining the fire endurance rating other than through testing. This has resulted in non-acceptance of many assemblies for which an experimental fire endurance rating was not available. To permit use of "non-listed" assemblies, a methodology for calculating the fire endurance of load bearing and non-load bearing floor, wall, ceiling and roof assemblies has been adapted for use. A number of building codes now accept fire endurance ratings developed by this "Component Additive Method" (CAM) calculation methodology. |
|
| COMPONENT
ADDITIVE METHOD (CAM)
History
|
![]() |
| Use
and Application
Combining results of the fire tests and basis provided by the Ten Rules, a methodology for calculating fire endurance ratings was developed. The review of full-scale wood-framed assembly fire tests by the Fire Test Board validated the methodology. These tests included both load bearing and non-load bearing assemblies with wood, gypsum wallboard and other membranes. Fire endurance ratings ranged from 20 to 90 minutes. In developing the methodology, the Fire Test Board broke down the fire endurance of the assembly into the fire endurance contribution of the exposed membrane and the time to destruction of the framing members. As a result, the calculated fire endurance would equal the sum of 1) the contribution of the fire exposed membrane, 2) the time to failure of the framing members, and if applicable 3) any additional protection due to use of cavity insulation or reinforcement of the membrane. The times assigned to protective wall and ceiling coverings are given in Table 1. These times are based on the ability of the membrane to remain in place during fire tests. This "assigned time" should not be confused with the "finish" rating of the membrane. The "finish rating" is the time it takes for the temperature to rise 250° F on the unexposed surface of a material when the material is exposed to a heat source following the ASTM E 119 Time-Temperature curve. As shown in Table 1, some pairs of membranes have been tested resulting in greater fire endurance times than the sum of the ratings of the individual membranes, in accordance with Harmathy’s rule #1. The times assigned to wood studs and joists were determined based upon the time it takes for the framing members to fail after failure of the protective membrane. The fire endurance time assigned to framing members is given in Table 2. These times are based on the ability of framing members to provide structural support when subjected to the ASTM E 119 fire endurance test without the benefit of a protective membrane. These time values are in part the result of full-scale tests of unprotected wood studs and floor joists where the structural elements were loaded to design capacity. They apply to all framing members and do not increase if, for example, 2 by 6 inch studs are used rather than 2 by 4 inch studs as implied by Harmathy’s rule #5. WALLS
In developing this methodology it was also determined that the primary function of the membrane on the unexposed side of an exterior wall is to keep the insulation in place and prevent the transmission of heat. Fire endurance of wall assemblies is consistently dependent upon the fire exposed-side membrane. As a result, it is considered very reasonable to substitute various exterior cladding materials as the membrane on the unexposed side or exterior wall assemblies1. Therefore, where a fire endurance rating for an exterior wall is to be determined using CAM, any combination of sheathing, paper, and exterior finish listed in Table 4 may be used, or the outer membrane may consist of any membrane combination that is assigned a time for contribution to fire endurance of at least 15 minutes in Table 1. ROOFS AND
FLOOR/CEILING ASSEMBLIES
|
![]() |
![]() ![]() |
| 1For examples of fire rated exterior walls see Design for Code Acceptance No. 3: Fire Rated Wood Wall Assemblies, American Forest & Paper Association, 2000. |
| EXAMPLE
CALCULATIONS
Example 1: Determine the fire endurance rating of a wall assembly having one layer of 5/8 inch Type X gypsum wallboard attached to wood studs on the fire exposed side (interior, see Figure 1). Table 1 shows that 5/8 inch Type X gypsum wallboard has a fire endurance time of 40 minutes. Table 2 shows that wood studs spaced 16 inches on center have a fire endurance time of 20 minutes. (Adding additional membranes to the framing would also be permitted according to Harmathy’s rule #2. If the wall is assumed to be exposed to fire from both sides (e.g., for interior fire rated partitions), each surface of the framing member would be required to be fire protected with at least 40 minutes of membrane coverings in Table 1. If the proposed wall is assumed to be exposed to fire from one side only, as is required of an exterior wall, the fire exposure is assumed to be from the interior, which would require a total contribution of 40 minutes from the membrane coatings from Table 1. It should be noted that to achieve the assigned fire endurance rating, the exterior side must be protected in accordance with Table 4 or any membrane that is assigned a time of at least 15 minutes as listed in Table 1. If wall cavities between studs
had been filled with rockwool insulation adding 15 minutes of fire endurance,
as noted in Table 3, the 5/8" Type X gypsum wallboard could be replaced
by ½" Type X gypsum wallboard. Thus, adding the fire endurance contribution
times for the ½ inch gypsum wallboard, wood studs, and insulation
(25 minutes + 20 minutes + 15 minutes) the resultant fire endurance rating
for the wall would also equal 60 minutes.
|
|
|
Example 2: Determine the fire endurance rating of a floor/ceiling assembly having wood joists spaced 16 inches on center and protected on the bottom side (ceiling side) with two layers of ½ inch Type X gypsum wallboard and having a ½ inch plywood subfloor on the upper side (floor side). Table 1 shows that the fire endurance time for each layer of ½ inch Type X gypsum wallboard is 25 minutes. The fire endurance time assigned for wood joists, as shown in Table 2, is 10 minutes. Adding the assigned times of two layers
of gypsum wallboard and wood joists, a fire endurance rating of 60 minutes
or one hour is calculated.
|
|
|
Example 3: A private residence is being changed to an office. The load bearing exterior walls of the residence consist of 2 by 4 inch studs spaced 16 inches on center, ½ gypsum wallboard on the inside, and 5/16 inch exterior grade plywood, sheathing paper and ¼ inch hardboard siding on the outside. The cavities between the wood studs are filled with ¼ lb/sq.ft. glass fiber batts. The code requires the exterior wall of the structure to be upgraded to one hour fire endurance with fire exposure from the inside only. What modifications can be made to comply with the code requirement? Table 1 shows the ½ inch gypsum wallboard has a contribution to the assembly fire rating of 15 minutes. According to Table 2, the studs have an assigned time of 20 minutes. According to Table 3, the glass fiber does not contribute to the fire endurance of a load bearing wall. Thus, the fire endurance rating of the exterior wall of the residence equals 35 minutes. In order to upgrade the wall to one hour, a protective membrane should be added on the inside, contributing 25 minutes or more to the assembly rating. For example, a ½ inch Type X gypsum wallboard adds 25 minutes according to Table 1, leading to a total of 60 minutes. |
|
|
|
The
procedure described in this publication is intended to assist the designer
of wood-frame structures in meeting specified fire endurance requirements.
Special effort has been made to insure the accuracy of the information
presented. However, AF&PA does not assume responsibility for particular
designs or calculations prepared from this publication.
For additional information or assistance contact: American Forest & Paper Association
COPYRIGHT Ó
2001
|
| 2Code Conforming Wood Design: Free Windows-based software providing summary of allowable wood uses, including height and area requirements. Available at http://www.awc.org. |