Building
Code Requirements For
occupancies such as stores, apartments, offices, and other commercial
and industrial uses, building codes commonly require floor/ceiling
and wall assemblies to be fire-resistance rated in accordance
with standard fire tests.
Depending on the application, wall assemblies
may need to be rated either from one side or both sides. For
specific exterior wall applications, the 2000 International
Building Code (IBC), the 1999 National Building
Code (NBC), and the 1999 Standard Building Code (SBC)
allow wood-frame, wood-sided walls to be tested for exposure
to fire from the inside only. Rating for both interior and
exterior exposure is only required when the wall has a fire
separation distance of less than 5 feet. Code recognition of
one and two-hour wood-frame wall systems is also predicated
on successful fire and hose stream testing in accordance with ASTM
E119, Standard Test Methods for Fire Tests of Building Construction
Materials.
Fire Tested Assemblies
Fire-rated wood-frame assemblies
can be found in a number of sources including the IBC, Underwriters
Laboratories (UL) Fire Resistance |
| Directory,
Intertek Testing Services' Directory of Listed Products,
and the Gypsum Association's Fire Resistance Design Manual.
The American Forest & Paper Association (AF&PA) and
its members have tested a number of wood-frame fire-rated
assemblies. Descriptions of these successfully tested assemblies
are provided in Table 1 for one-hour
rated wall assemblies, Table 2 for
two-hour rated wall assemblies, Table 3 for
one-hour rated floor/ceiling assemblies, and Table
4 for two-hour rated floor/ceiling assemblies. Additional
tests are being conducted and the Tables will be updated
periodically. |
|
Conclusions
Wood-frame assemblies
are used in architectural designs because of their adaptability
to style preferences, ease and economies of construction, and
energy-saving performance. |
|
|
Table 1: One-Hour
Fire-Rated Loadbearing Wood-Frame Wall Assemblies
|
| Assemblies
Rated From Both Sides |
|
Studs
|
Insulation
|
Sheathing
on Both Sides
|
Fasteners
|
Details
|
| 2x4 @ 16" o.c. |
3½" mineral wool batts |
5/8" Type X Gypsum Wallboard (H) |
2¼" #6 Type S drywall screws @ 12" o.c. |
WS4-1.1
|
| 2x6 @ 16" o.c. |
(none) |
5/8" Type X Gypsum Wallboard (H) |
2¼" #6 Type S drywall screws @ 7" o.c. |
WS6-1.1
|
| 2x6 @ 16" o.c. |
5½" mineral wool batts |
5/8" Type X Gypsum Wallboard (H) |
2¼" #6 Type S drywall screws @ 12" o.c. |
WS6-1.2
|
| 2x6 @ 16" o.c. |
R-19 fiberglass insulation |
5/8" Type X Gypsum Wallboard (V) |
2¼" #6 Type S drywall screws @ 12" o.c. |
WS6-1.4
|
|
Assemblies
Rated From One Side (Fire on Interior Only)
|
|
Studs
|
Insulation
|
Sheathing
|
Fasteners
|
|
| 2x4 @ 16" o.c. |
3½" mineral wool batts |
I
|
5/8" Type X Gypsum Wallboard (H) |
2¼" #6 Type S drywall screws @ 12" o.c. |
WS4-1.2
|
|
E
|
3/8" wood structural panels (V) |
6d common nails @ 6" edges/12" field |
| 2x4 @ 16" o.c. |
4 mil polyethylene 3½" mineral wool batts |
I
|
5/8" Type X Gypsum Wallboard (V) |
6d cement coated box nails @ 7" o.c. |
WS4-1.3
|
|
E
|
½" fiberboard (V) |
1½" roofing nails @ 3" edges/6" field |
| 3/8" hardboard shiplapped panel siding |
8d galv. nails @ 4" edges/8" field |
| 2x6 @ 16" o.c. |
5½" mineral wool batts |
I
|
5/8" Type X Gypsum Wallboard (H) |
2¼" #6 Type S drywall screws @ 12" o.c. |
WS6-1.3
|
|
E
|
7/16" wood structural panels (V) |
6d common nails @ 6" edges/12" field |
| 2x6 @ 16" o.c. |
R-19 fiberglass insulation |
I
|
5/8" Type X Gypsum Wallboard (V) |
2¼" #6 Type S drywall screws @ 12" o.c. |
WS6-1.5
|
|
E
|
3/8" wood structural panels (V) |
6d common nails @ 6" edges/12" field |
H-
applied horizontally with vertical joints over studs I-
Interior sheathing
V- applied vertically with vertical joints
over studs E-
Exterior sheathing |
|
Table 3: One-Hour
Fire-Rated Wood Floor/Ceiling Assemblies
|
|
Wood
I-Joist Assemblies
|
|
Joists
|
Insulation
|
Furring |
Ceiling
Sheathing
|
Fasteners
|
Details
|
I-joists @ 24" o.c.
Min. flange thickness: 1-1/2"
Min. flange area: 5.25 sq. in.
Min. web thickness: 3/8"
Min. I-joist depth: 9-1/4" |
1-1/2" mineral wool batts
(2.5 pcf - nominal)
Resting on hat-shaped channels |
Hat-shaped
channels |
F |
5/8" Type C Gypsum Wallboard |
1-1/8" Type S drywall screws
@ 12" o.c.
see fastening details)
|
WIJ-1.1
|
I-joists @ 24" o.c.
Min. flange thickness: 1-1/2"
Min. flange area: 5.25 sq. in.
Min. web thickness: 7/16"
Min. I-joist depth: 9-1/4" |
1-1/2" mineral wool batts
(2.5 pcf - nominal)
Resting on resilient channels |
Resilient
channels |
F |
5/8" Type C Gypsum Wallboard |
1" Type S drywall screws @
8" o.c.
(see fastening details)
|
WIJ-1.2
|
I-joists @ 24" o.c.
Min. flange thickness: 1-5/16"
Min. flange area: 2.25 sq. in.
Min. web thickness: 3/8"
Min. I-joist depth: 9-1/4" |
2" mineral wool batts
(3.5 pcf - nominal)
Resting on 1x4 setting strips |
Resilient
channels |
F |
5/8" Type C Gypsum Wallboard |
1-1/8" Type S drywall screws
@ 7" o.c.
(see fastening details)
|
WIJ-1.3
|
I-joists @ 24" o.c.
Min. flange thickness: 1-1/2"
Min. flange area: 3.45 sq. in.
Min. web thickness: 3/8"
Min. I-joist depth: 9-1/4" |
1" mineral wool batts
(6 pcf - nominal)
Resting on hat-shaped channels
under I-joist bottom flange |
Hat-shaped
channels
supported by
CSC clips |
F |
1/2" Type C Gypsum Wallboard |
1" Type S drywall screws @
12" o.c.
(see fastening details)
|
WIJ-1.4
|
I-joists @ 24" o.c.
Min. flange thickness: 1-1/2"
Min. flange area: 2.25 sq. in.
Min. web thickness: 3/8"
Min. I-joist depth: 9-1/4" |
(none)
|
(none)
|
B |
1/2" Type X Gypsum Wallboard |
1-5/8" Type S drywall screws
@ 12" o.c. |
WIJ-1.5
|
| F |
1/2" Type X Gypsum Wallboard |
2" Type S drywall screws @
12" o.c.
1-1/2" Type G drywall screws @ 8" o.c.
(see fastening details)
|
I-joists @ 24" o.c.
Min. flange thickness: 1-5/16"
Min. flange area: 1.95 sq. in.
Min. web thickness: 3/8"
Min. I-joist depth: 9-1/2" |
(optional)
|
Resilient
channels |
B |
1/2" Type X Gypsum Wallboard |
1-1/4" Type S drywall screws
@ 12" o.c. |
WIJ-1.6
|
| F |
1/2" Type X Gypsum Wallboard |
1-5/8" Type S drywall screws
@ 12" o.c.
1-1/2" Type G drywall screws @ 8" o.c.
(see fastening details)
|
| B- Base
layer sheathing F-
Face layer sheathing |
|
Table 4: Two-Hour
Fire-Rated Wood Floor/Ceiling Assemblies
|
|
Wood
I-Joist Assemblies
|
|
Joists
|
Insulation
|
Furring |
Ceiling
Sheathing
|
Fasteners
|
Details
|
I-joists @ 24" o.c.
Min. flange thickness: 1-1/2"
Min. flange area: 2.25 sq. in.
Min. web thickness: 3/8"
Min. I-joist depth: 9-1/4" |
3-1/2" fiberglass
insulation
Supported by stay wires spaced
12" o.c.
|
(none)
|
B |
5/8" Type C Gypsum Wallboard |
1-5/8" Type S drywall screws
@ 12" o.c. |
WIJ-2.1
|
Hat-shaped
channels |
M |
5/8" Type C Gypsum Wallboard |
1" Type S drywall screws @
12" o.c. |
| F |
5/8" Type C Gypsum Wallboard |
1-5/8" Type S drywall screws
@ 8" o.c.
(see fastening details)
|
| B- Base
layer sheathing (direct attached) M-
Middle layer sheathing F-
Face layer sheathing |