WS6-1.3 One-Hour Fire-Resistive Wood-Frame Wall Assembly
2x6 Wood Stud Wall - 100% Design Load - ASTM E 119 / NFPA 251

1. Framing - Nominal 2x6 wood studs, spaced 16 in. o.c., double top
plates, single bottom plate
2. Interior Sheathing - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied
horizontally. Horizontal joints are unblocked. Horizontal application of wallboard
represents the direction of least fire resistance as opposed to vertical application.
of least fire resistance as opposed to vertical application.
3. Exterior Sheathing - 7/16 in. wood structural panels (oriented strand board), applied vertically, horizontal joints blocked
4. Gypsum Fasteners - 2-1/4 in. #6 Type S drywall screws, spaced 12 in. o.c.
5. Panel Fasteners - 6d common nails (bright) - 12 in. o.c. in the field, 6 in. o.c. panel edges
6. Insulation - 5-1/2 in. thick mineral wool insulation (2.5 pcf, nominal)
7. Joints and Fastener Heads - Wallboard joints covered with paper
tape and joint compound, fastener heads covered with joint compound
Tests conducted at the Fire Test Laboratory of National Gypsum Research
Center
Test No: WP-1244 (Fire Endurance & Hose Stream) February 25, 2000
Third Party Witness: Intertek Testing Services
Report J99-27259.2
| This assembly was tested at 100% design load, calculated in accordance with the 2005 National Design Specification® for Wood Construction. The authority having jurisdiction should be consulted to assure acceptance of this report. |