WS4-1.2 One-Hour Fire-Resistive Wood Wall Assembly
2x4 Wood Stud Wall - 100% Design Load - ASTM E 119 / NFPA 251


1. Framing - Nominal 2x4 wood studs, spaced 16 in. o.c., double top plates, single bottom plate
2. Interior Sheathing - 5/8 in. Type X gypsum wallboard, 4 ft. wide, applied horizontally, unblocked. Horizontal application of wallboard represents the direction of least fire resistance as opposed to vertical application.
3. Exterior Sheathing - 3/8 in. wood structural panels (oriented strand board), applied vertically, horizontal joints blocked
4. Gypsum Fasteners - 2-1/4 in. Type S drywall screws, spaced 12 in. o.c.
5. Panel Fasteners - 6d common nails (bright) - 12 in. o.c. in the field, 6 in. o.c. panel edges
6. Insulation - 3-1/2 in. thick mineral wool insulation (2.5 pcf, nominal)
7. Joints and Fastener Heads - Wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound

Tests conducted at the Fire Test Laboratory of National Gypsum Research Center
Test No:      WP-1261 (Fire Endurance & Hose Stream)      November 1, 2000

Third Party Witness: Intertek Testing Services
                                  Report J20-006170.2

This assembly was tested at 100% design load, calculated in accordance with the 1997 National Design Specification® for Wood Construction. The authority having jurisdiction should be consulted to assure acceptance of this report.

                Copyright © 2000
AMERICAN WOOD COUNCIL                   AMERICAN FOREST & PAPER ASSOCIATION, INC                 NOVEMBER 2000