WIJ-1.5 One-Hour Fire-Resistive Ceiling Assembly
Floora/Ceiling - 100% Design Load - 1 Hour Rating - ASTM E 119 / NFPA 251

1. Floor Topping (optional, not shown): Gypsum concrete, lightweight or normal concrete topping.
2. Floor Sheathing: Minimum 23/32 inch thick tongue-and-groove wood sheathing (Exposure 1). Installed per code requirements with minimum 8d common nails.
3. Structural Members: Wood I-joists spaced a maximum of 24 inches on center.
      Minimum I-joist flange depth: 1-1/2 inches Minimum I-joist flange area: 2.25 inches2
      Minimum I-joist web thickness: 3/8 inch Minimum I-joist depth: 9-1/4 inches
     
Types of Adhesives Used in Tested I-Joists
LVL Flange Adhesive Flange-to-Web Joint Web-to-Web Endjoint
Phenol-Resorcinol-Formaldehyde Phenol-Resorcinol-Formaldehyde Phenol-Resorcinol-Formaldehyde

4. Gypsum Wallboard: Two layers of minimum 1/2 inch Type X gypsum wallboard attached with the long dimension perpendicular to the I-joists as follows:
      4a. Wallboard Base Layer: Base layer of wallboard attached to bottom flange of I-joists using 1-5/8 inch Type S drywall screws at 12 inches on center. End joints of wallboard centered on bottom flange of the I-joist and staggered.
      4b. Wallboard Face Layer: Face layer of wallboard attached to bottom flange of I-joists through base layer using 2 inch Type S drywall screws spaced 12 inches on center on intermediate joists and 8 inches on center at end joints. Edge joints of wallboard face layer offset 24 inches from those of base layer. End joints centered on bottom flange of I-joists and offset a minimum of one joist spacing from those of base layer. Additionally, wallboard face layer attached to base layer with 1-1/2 inch Type G drywall screws spaced 8 inches on center, placed 6 inches from face layer end joints.
5. Finish System (not shown): Face layer joints covered with tape and coated with joint compound. Screw heads covered with joint compound.

      Fire Tests conducted at Factory Mutual Research September 29, 1978
      Third Party Witness: Factory Mutual Research Report No: FC-268
      PFS Test Report #86-09-1 July 28, 1986

STC and IIC Sound Ratings for Listed Assembly
Without Gypsum Concrete With Gypsum Concrete
Cushioned Vinyl Carpet & Pad Cushioned Vinyl Carpet & Pad
STC IIC STC IIC STC IIC STC IIC
- - - - - - 49 b 55 b
a This assembly may also be used in a fire-rated roof/ceiling application, but only when constructed exactly as described.
b STC and IIC values estimated by David L. Adams Associates, Inc