| Where
specific fire resistance times are required, performance of wood members
over such periods may be calculated as follows:
Beams:
(1) fire exposure on four
sides
t = 2.54 z b [4-2(b/d)]
(2) fire exposure on three
sides
t = 2.54 z b [4-(b/d)]
where:
b = breadth (width) of beam before fire exposure
(in inches)
d = depth of beam before fire exposure (in inches)
z = load factor (see
Figure
1 )
= 1.3
for r <= 0.5
= 0.7 + 0.3/r for r > 0.5
r = ratio of induced load to maximum allowable
load
t = fire endurance (in minutes)
Columns:
(1) fire exposure on four
sides
t = 2.54 z d [3-(d/b)]
(2) fire exposure on three
sides
t = 2.54 z d [3-(d/b)/2]
where:
b = maximum dimension of column before fire
exposure (in inches)
d = minimum dimension of column before fire
exposure (in inches)
z = load factor (see
Figure
1)
= 1.5
for KeL/d <= 11 and r <= 0.5
= 0.9 + 0.3/r for KeL/d <=
11 and r > 0.5
= 1.3
for KeL/d > 11 and r <= 0.5
= 0.7 + 0.3/r for KeL/d
> 11 and r > 0.5
r = ratio of induced load to maximum allowable
load
Ke= effective length factor (see
Figure
2 )
L = effective length (in inches)
t = fire endurance (in minutes)
Each of the foregoing equations
relates endurance time to the percent of maximum allowable design load
applied and cross section dimensions. For given member sizes, different
endurance times can be achieved by varying the percent of maximum design
load applied to the member. Examples of |
relationships
between load and endurance time for wood beams exposed on three sides are
shown in Figure 3.
Application
The formula for columns
exposed to fire on three sides applies only when the unexposed face is
the smaller column dimension. Where the column is recessed in a wall, its
full dimension shall be used for the purpose of the calculations.
Allowable loads on beams
and columns are determined using design procedures from the National
Design Specification® for Wood Construction (NDS®).
Glued laminated timber beams
utilize standard laminating combinations except that a core lamination
is removed, the tension zone is moved inward, and the equivalent of an
extra nominal 2-inch thick outer tension lamination is added.
Where one-hour fire endurance
is required, connectors and fasteners must be protected from fire exposure
by 1.5 inches of wood, fire-rated gypsum board, or any coating approved
for a one-hour rating. Typical details for commonly used fasteners and
connectors in timber framing are shown in Figure 4
(Beam to Column Connection Not Exposed to Fire), Figure
5 (Beam to Column Connection Exposed to Fire Where Appearance is a
Factor), Figure 6 (Ceiling Construction), Figure
7 (Beam to Column Connection Exposed to Fire Where Appearance is Not
a Factor),
Figure 8 (Column Connections - Covered),
Figure
9 (Beam to Girder - Concealed Connection).
The procedure described
in this brochure is intended to assist the designer of timber framed structures
in achieving predictable performance within specified fire endurance requirements.
Special effort has been made to assure that the information reflects the
state of the art. However, the American Forest & Paper Association
does not assume responsibility for particular designs or calculations prepared
from this publication.
For additional information
or assistance contact:
American Forest & Paper
Association
1111 19th Street, NW, Suite
800
Washington, DC 20036
www.awc.org
202-463-4713
Copyright (c) 2001 American
Forest & Paper Association, Inc.
May 2000 Revision
pdf version also available
(10 pg, 1.1 MB). |